Foreword
This
guide is presented to serve as an aid for designers who are becoming
familiar with pervious concrete to be used as a light traffic parking lot
pavement and a stormwater management device.
1.0 General
Provision
Scope of Work:
The
work to be completed under this contract includes the furnishing of all
labor,
materials, and equipment necessary for construction of the project in
conformance with the plans and specifications.
2.0
Reference Documents:
American Society of Testing and Materials
ASTM
C 29
Test Method for Unit Weight and Voids in Aggregate
ASTM C 33
Specifications for Concrete Aggregates
ASTM C 42
Test Methods for Obtaining and Testing Drilled Cores and Sawed
Beams of Concrete
ASTM
C 94
Standard Specification for Ready Mix Concrete
ASTM C 117 Test
Method for Material Finer than 75 µm (No. 200) Sieve in Mineral
Aggregates by Washing
ASTM C 138 Test
Method for Unit Weight, Yield, and Air Content (Gravimetric) of Concrete
ASTM C 140 Methods
of Sampling and Testing Concrete Masonry Units
ASTM C 150 Specifications
for Portland Cement (Types I or II only)
ASTM C 172 Practice
of Sampling Fresh Concrete
ASTM C 260 Specification
for Air-Entraining Admixtures for Concrete
ASTM C 494 Specification
for Chemical Admixtures for Concrete
ASTM C 595 Specifications
for Blended Hydraulic Cements (Types IP or IS only)
ASTM C 618 Specification
for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use as a Mineral
Admixture in Portland Cement Concrete
ASTM
D 698 Tests
for Moisture-Density Relations of Soils and Soil Aggregate Mixtures Using
5.5 Pound
Rammer and 12-inch Drop
ASTM C 989 Specification
for Ground Granulated Blast Furnace Slag for Use in Concrete and Mortars
ASTM C 1077 Practice
for Laboratories Testing Concrete and Concrete Aggregates for Use in
Construction and
Criteria for Laboratory Evaluation
ASTM
C1157 Performance
Specifications for Hydraulic Cement
ASTM
C 1602 Specification
for Mixing Water Used in the Production of Hydraulic Cement Concrete
ASTM
D 2487 Standard
Practice for Classification of Soils for Engineering Purposes
ASTM
D 3385 Standard
Test Method for Infiltration Rate of Soils In Field Using
Double-Ring Infiltrometer
ASTM
E 329 Standard
Recommended Practice for Inspection and Testing Agencies for Concrete,
Steel and
Bituminous Materials as Used in Construction
American Association of State Highway and Transportation Officials
(AASHTO)
Use standards comparable to listed ASTM standards
Georgia
Department
of
Transportation (GDOT) Standard
Specifications Construction of Transportation Systems
Use standards comparable to listed ASTM standards
American Concrete Institute
ACI
305R Hot Weather Concreting
ACI
306R Cold Weather Concreting
ACI
522 Pervious Concrete
3.0
Contractor Qualifications:
Contractors should meet the requirements
of the Georgia Concrete and Products Association (GCPA) Pervious Concrete
Contractor Training Program. The requirements of the GCPA program, which
incorporates the National Ready Mix Concrete Association’s Pervious
Contractor Certification Program are:
Pervious
Technician
- Attend
GCPA’s Pervious Concrete Training Class
- Successfully
complete the NRMCA’s
Pervious Concrete Technician Exam
- Attend
GCPA’s Placement Demo
Pervious Installer:
Level I* :
- Successful
completion of the requirements for GCPA’s Pervious Technician
- Pass
the NRMCA Performance Test provided by GCPA.
Level
II**:
- Successful
completion of Level I Installer
- Successful
completion of 10 Pervious Concrete installations, at least 3 of which
have been tested and met the requirements for thickness and unit
weight as outlined below in this specification
Craftsman**:
Complete the requirements of NRMCA’s Pervious Concrete Craftsman
Program.
*
Successful installation of Test Panels outlined in this
specification are required.
* * Test
Panel required only if specified
Proposed Contractors, who have not been through the
GCPA training program or a comparable, industry recognized program, must
submit credentials and experience to the specifier for review and
determination if they satisfy the requirements of the project.
If
the placing contractor and concrete producer have insufficient experience
with Portland Cement Pervious Concrete Pavement, the placing contractor
shall retain an experienced consultant to monitor production, handling,
and placement operations at the contractor’s expense.
Test
Panels:
If
the pervious contractor is a GCPA Level I Installer or if directed by the
specifier, the pervious contractor is to place, joint and cure two test
panels of the lane width that will be used during placement for the
project, each a minimum of 225 sq. ft., at the required project thickness,
to demonstrate to the specifier’s satisfaction that the design criteria
can be achieved and a satisfactory pavement can be installed. During
placement, the concrete will be tested for density (unit weight) in
accordance with ASTM C 138 except that the Jigging Procedure in Section 11
of ASTM C 29 will be used to consolidate the concrete.
Test
panels shall be tested for thickness in accordance with ASTM C 42. Two
cores shall be taken from each test panel 7 days after placement. After
the cores are measured for thickness as described in ASTM C42, they shall
be measured for density (unit weight) in the saturated condition as
described in Section 8 of ASTM C 140, Standard Methods of Sampling and
Testing Concrete Masonry Units.
Satisfactory
performance of the test panels will be determined by:
Compacted
thickness within 1/4" of specified thickness
Void
Structure: 15% minimum, 25% maximum or within 4% of the specified void
content
Unit
weight ± five (5) pcf of the design unit weight
Visual
observation finds no clogging, paste drain down or poorly hydrated paste
If
the test panel(s) meets these, it(they) can be left in-place and included
in the completed work. If so directed by the specifier or owner, the
pervious contractor will remove and dispose of test panels which do not
meet specification requirements.
4.0 Concrete Mix Design:
Contractor
shall furnish a proposed mix design with proportions of materials to owner
or specifier prior to commencement of work. The aggregate data shall
include unit weights determined in accordance with ASTM C 29 Section 11,
Jigging Procedure.
4.1
MATERIALS:
General:
Locally
available material having a record of satisfactory performance shall be
used.
Cement:
Portland
Cement Type I or II conforming to ASTM C 150, Type IP or IS conforming to
ASTM C 595 or Type GU or MS conforming to ATM C1157 may be used.
Flyash and Ground Iron Blast-Furnace Slag:
Flyash
shall conform to ASTM C 618
Ground
Granulated Blast-Furnace Slag (GGBFS) shall conform to ASTM C 989
Note:
When Flyash or GGBFS is used
as part of the minimum cementitious content , strength development may be
delayed and additional curing time maybe required. See Section 6.0.
Aggregate:
Use
a well graded aggregate with a maximum size no greater than ˝” meeting
the Deleterious Substances and Physical Property requirements of Class 5M
in Table 3 of ASTM C33. Typical acceptable gradations are No. 8 or 89 (max
size 3/8 inch) stone meeting ASTM C33 or GDOT gradations.
Submit aggregate data to specifier or owner for approval if another
gradation is proposed for use on the project.
Air Entraining Agent:
Shall
comply with ASTM C 260.
Admixtures:
Shall
meet ASTM C494 requirements for Type A Water reducing Admixtures, Type B
Retardingor Type D Water Reducing/Retarding
A
hydration stabilizer is recommended in the design and production of
pervious concrete. This admixture suspends cement hydration and delays
initial set. The admixture’s primary function should be as a hydration
stabilizer; however, it must also meet the requirements of ASTM C 494 Type
B Retarding or Type D Water Reducing/Retarding Admixtures. Viscosity
Modifying Admixtures, which increase the viscosity of the paste, have been
used successfully to aid in placement.
Water
Potable
or shall comply with ASTM C 1602 or GDOT Standard Specifications.
4.2
PROPORTIONS:
Cement Content:
For
pavements subjected to vehicular traffic loading, the total cementitious
material shall not be less than 600 lbs. per cu. yd. Flyash may be used in
amounts not to exceed 25% of total cementitious material. GGBFS may be
used in amounts not to exceed 50% by weight of total cementitious
material. Slag content should be reduced to 30% when ambient temperatures
fall below 50 F. If a ternary mix is used, the total replacement shall not
exceed 50% of the mass of the Portland cement.
Aggregate Content:
The
volume of aggregate per cu. yd. shall be equal to 27 cu. ft. when
calculated
as a function of the bulk unit weight determined in accordance with ASTM C
29, Jigging
Procedure. If used, fine aggregate should not exceed three (3) bulk cu.
ft., based on unit weight obtained by the Jigging Procedure, and shall be
included as part of the 27 cu. ft of total aggregate volume.
Admixtures:
Follow
the manufacturer’s instructions and recommendations.
Mix Water:
Mix
water quantity shall produce a fully wetted paste with high viscosity.
This condition occurs when the cement paste displays a wet, metallic sheen
and does not flow from the aggregate. An insufficient amount of water
yields a cement paste with a dull-dry appearance and insufficient water
for hydration.
Insufficient
water results in poor bond strength while high water content results in
the paste draining off the aggregate, sealing the bottom of the pervious
concrete and causing a weak pavement surface.
5.0
SUBGRADE PREPARATION AND FORMWORK:
Subgrade Material:
The
top 6 inches shall be composed of free draining, granular or gravely soil
that is predominantly sandy with no more than a moderate amount of silt or
clay. Where this type of subgrade is not present, a separation layer of
non woven geotextile fabric shall be placed on the subgrade followed by a
zone of clean gravel, such as #57 stone. This zone is referred to as the
recharge bed.
Subgrade Permeability:
Prior
to placement of Portland Cement Pervious Pavement, the subgrade shall be
tested for rate of permeability by double ring infiltrometer (ASTM D
3385), or other suitable test of subgrade soil permeability. The tested
permeability must meet the requirements of the project designer.
Subgrade Support:
The
subgrade shall be compacted by a mechanical vibratory compactor to a
minimum density of 95% of the maximum dry density as established by ASTM D
698 or AASHTO T 99. Subgrade permeability is inversely proportional to
compaction so care should be taken to avoid compaction levels that prevent
the subgrade from providing the permeability assumed in the design.
If
fill material (embankment) is required to bring the site to subgrade
elevation, it shall be clean and free of deleterious materials. It shall
be placed in accordance with the geotechnical engineer’s recommendations
and/or the project specifications. The subgrade shall be firm, compacted,
in a moist condition with no mud or standing water.
Forms:
Forms
may be of wood or steel and shall be the depth of the pavement. Forms
shall be of sufficient strength and stability to not deform under the
stresses caused by mechanical equipment used in spreading, strike-off and
compaction operations.
6.0 MIXING, HAULING AND PLACING:
Pervious Concrete should be produced,
delivered and discharged in accordance with ASTM C 94. It is important
that mixer trucks meet the Concrete Uniformity Requirements of Annex A1 of
C 94.
Mix and Placement Time:
Truck
mixers shall be operated at the speed designated as mixing speed by the
manufacturer for 75 to 100 revolutions of the drum. Placement, screeding,
compacting and jointing of the concrete mixture must be completed within
one (1) hour of the introduction of mix water, unless otherwise approved
by the owner or specifier. This time can be increased to 90 minutes when
utilizing the hydration stabilizer specified in Section 4.1 or when cool,
humid and calm weather conditions exist.
Discharge:
Each
mixer truck will be inspected for appearance of consistency described in
4.2 and for concrete uniformity. Water may be added to obtain the required
mix consistency. A minimum of 20 revolutions at the manufacturer’s
designated mixing speed shall be required following any addition of water
to the mix. Discharge shall be a continuous operation and shall be
completed as quickly as possible. Concrete shall be deposited as close to
its final position as practicable and such that fresh concrete enters the
mass of previously placed concrete. The practice of discharging onto
subgrade and pulling or shoveling to final placement is to be avoided.
Placing and Finishing Equipment:
The
contractor will be restricted to pavement placement widths of a maximum of
fifteen (15) feet
unless the contractor can demonstrate competence in constructing greater
pavement placement widths to the satisfaction of the owner or specifier.
Unless
otherwise approved by the owner and specifier in writing, the contractor,
shall provide mechanical equipment of either slipform or form riding with
a following compactive unit that will provide a minimum of 10 psi vertical
pressure. If placing equipment does not provide the minimum specified
vertical force, a full width roller or other full width compaction device
that provides sufficient compactive effort shall be used immediately
following the strike-off operation.
It
is typical that riser strips are attached to the top of the form to allow
the screeding/strike-off equipment to level the concrete Ľ to ˝ inch
thick above design top of pavement. The mix design, pavement thickness and
compactive effort will determine how far the screed elevation is above top
of pavement. After screeding, the riser strips are removed and compaction
rollers consolidate the concrete to finish grade. Cross rolling may be
required to obtain the required pavement surface planeness. The pervious
concrete pavement will be placed to the required cross section and shall
not deviate more than ± 3/8 inch in 10 feet from profile grade.
After
the compaction operation, no other finishing operation will be allowed. If
vibration is used, it shall be shut off immediately when forward progress
is halted for any reason.
Jointing:
Transverse
control (contraction) joints shall be installed at 20 foot intervals. They
shall be installed at a depth of at least 1/4 the thickness of the
pavement. Longitudinal control joints shall be installed at the midpoint
of the placement if the constructed lane width exceeds 20 feet. Where
joints are installed, it is highly recommended that they be cut into the
fresh concrete during placement using a “pizza cutter” roller
specifically constructed for the purpose. If saw cut, the procedure should
begin as soon as the pavement has hardened sufficiently to prevent
raveling and uncontrolled cracking (normally after curing).
Transverse
construction joints shall be installed whenever placing is suspended a
sufficient length of time that concrete may begin to harden. In order to
assure aggregate bond at construction joints, a bonding agent suitable for
bonding fresh concrete to existing concrete shall be brushed, rolled, or
sprayed on the existing pavement surface edge. Isolation (expansion)
joints will not be used except when pavement is abutting slabs or other
adjoining structures.
Curing:
Curing
procedures shall begin immediately following placement operations. The
pavement surface shall be covered with a minimum six (6) mil thick
polyethylene sheet or other approved non absorptive, water impermeable
covering material within 30 minutes of concrete discharge from the truck.
Prior to covering, a fog or light mist shall be sprayed above the surface
when required to replace water which evaporated due to ambient conditions
(temperature, wind, and low humidity). The cover shall overlap all exposed
edges and shall be thoroughly secured (without using soil or other fine
material which is subject to be displaced by wind or water) to completely
encapsulate the pervious concrete and to prevent dislocation due to winds
or adjacent traffic conditions.
Due
to the porosity of pervious concrete allowing dissipation of its heat of
hydration, it is critical that cold weather concrete practices stipulated
in ACI 306 be used when cooler temperatures are experienced during
construction.
Cure
Time:
The polyethylene curing sheet shall be left in place for the durations
shown:
Portland
Cement Type I, II or IS; Hydraulic Cement Type GU or MS - 7 days minimum
GGBFS
or Class F Flyash as part of the 600 lbs./cy minimum cementitious or Type
IP - 10 days minimum unless test data indicates that the concrete reaches
sufficient maturity at an earlier age
No
truck traffic shall be allowed for 10 days (no passenger car/light trucks
for
seven (7) days) or the minimum cure time is reached.
7.0
TESTING, INSPECTION AND ACCEPTANCE:
Laboratory Qualification:
The
owner will retain an independent testing laboratory which shall conform to
the applicable requirements of ASTM E 329, Standard Recommended
Practice for Inspection and Testing Agencies for Concrete, Steel, and
Bituminous Materials as Used in Construction, and ASTM C 1077, Standard
Practice for Testing Concrete and Concrete Aggregates for Use in
Construction, and Criteria for Laboratory Evaluation, and shall be
inspected
and accredited by a recognized national authority.
The
agent of the testing laboratory performing field sampling and testing for
concrete shall be certified by the American Concrete Institute as a
Concrete Field Testing Technician Grade I, or be of an equivalent level of
competence as certified
by a recognized state or national authority. It is highly recommended that
the agent be a certified NRMCA Pervious Technician.
Testing and Acceptance:
A
minimum of one soil classification test in accordance with ASTM C2487
shall be performed for each day’s placement of pervious concrete.
A
minimum of one sample for each days placement shall be taken in accordance
with ASTM C 172. Delivered unit weights are to be determined in accordance
with ASTM C 29, paragraph 11, Jigging Procedure, using at least a 0.25
cubic foot cylindrical metal measure. The unit weight of the delivered
concrete shall be ± five (5) pcf of the mix design unit weight.
A
minimum of seven (7) days after each placement, three cores shall be taken
in accordance with ASTM C 42. The cores shall be measured for thickness
and unit weight and visually observed as described above for Test Panels.
Core holes shall be filled with concrete meeting the pervious mix design.
The
average of all production cores shall not be less than the specified
thickness with no individual core being more than ˝ inch less than the
specified thickness. The average void content of the cores shall be within
4% of the specified void content with no individual void content being
less than 15% or 5% greater than the specified void content. Visual
observation shall find no clogging, paste drain down or poorly hydrated
paste.
SPECIAL
NOTE:
This information is intended to be used by the design professional
competent to evaluate its significance and limitation and who will accept
the responsibility for its proper application. The Georgia Concrete and
Products Association disclaims any and all responsibility for any other
use of the information supplied herein.
Revised
August 2006
Download
this document in
printer-friendly Microsoft Word format